€ 16,900.00
The Honeywell TMG740-3 is a sequence control box designed for medium to high-performance forced-draught and dual-fuel oil or gas burners operating in intermittent mode. It supports single-stage or two-stage operation, includes flame supervision (via ionisation probe, UV sensor or IR flicker detector), and offers monitored air-proving and damper/valve interlocks for safe combustion system start-up and shutdown.
In stock
Overview
The Honeywell TMG740-3 is a sequence control box designed for medium to high-performance forced-draught and dual-fuel oil or gas burners operating in intermittent mode. It supports single-stage or two-stage operation, includes flame supervision (via ionisation probe, UV sensor or IR flicker detector), and offers monitored air-proving and damper/valve interlocks for safe combustion system start-up and shutdown.
Key Features
Supply voltage 220-240 V AC (50 Hz) version (Mod. 43-35)
Controls burners with pilot valve, main valve(s) and provides flame supervision and lock-out diagnostics
Supports ionisation, UV and IR flame detection technologies
Monitored air-proving switch, damper position feedback for safe start sequence
Manual reset button with signal lamp for lock-out indication
Compact control box for mounting on wiring base
Approved to relevant European burner safety standards
Main Benefits
Ensures safe, reliable burner start sequence with pre-purge, ignition, flame supervision and post-purge as needed
Flexible use with gas, oil or dual fuel burners in industrial or commercial installations
Integrated diagnostics and signal indication reduce maintenance time and increase system uptime
Compatible with many flame detectors and wiring bases for retrofit or new install
Established brand and long availability of spares and support
Technical Highlights
Supply voltage: 220-240 V AC (-15 % / +10 %) at 50 Hz
Fuse rating: 10 A fast or 6 A slow
Power consumption approx. 15 VA
Output terminals max current: 4 A per terminal, total up to 6 A
Ambient temperature range: -20 °C to +60 °C
Mounting attitude: any
Protection class: IP44
Weight (incl. base) approx. 1.1 kg
Installation & Safety Notes
Installation must be performed by qualified personnel in accordance with local regulations for combustion systems and electrical wiring.
Ensure correct wiring base is used and flame detector type matches the amplifier settings.
Confirm correct air-proving switch and damper feedback wiring to prevent unsafe burner start.
Ensure wiring length for flame detector remains within manufacturer spec to maintain sensitivity.
Check lock-out diagnostics and reset lamp operation before commissioning.
Applications
Industrial/commercial oil or gas burners in forced-draught systems
Dual-fuel burner installations requiring safety sequence control
Retrofitting burner control boxes in existing combustion systems
Compliance with EN 298 / burner safety regulations
| Weight | 1.2 kg |
|---|---|
| Dimensions | 9 × 7 × 5 cm |